Skip to content

Cracked furnace heat exchanger and flue backdrafting

Emergency numbers differ by country. This page uses 911, the number for the United States and Canada. Many other countries use 112, 999, or another number. Find the number for your country.

Every natural gas, liquid propane, and fuel oil central heating furnace relies on a sealed, thin-walled metal chamber called the heat exchanger to keep toxic combustion exhaust physically separated from the breathable warm air blown through your home's ductwork. Inside the heat exchanger tubes, gas burners generate flame temperatures exceeding 900 to 1,100 degrees Celsius (1,650 to 2,000 degrees Fahrenheit), producing carbon dioxide, water vapor, nitrogen oxides, and, whenever combustion is incomplete or starved of oxygen, lethal concentrations of carbon monoxide (\(CO\)) and pungent aldehydes. Meanwhile, a high-volume squirrel-cage circulating blower fan pushes household room air across the outside of those hot metal tubes and distributes it into every bedroom and living area.

Over 10 to 20 years of relentless thermal expansion and contraction cycles (heating from room temperature to 260 degrees Celsius / 500 degrees Fahrenheit and cooling back down thousands of times each winter), the aluminized or stainless steel walls of the heat exchanger fatigue, rust, and split open. Simultaneously, a blocked chimney flue, a failed draft inducer fan, or extreme negative indoor air pressure caused by powerful kitchen range hoods, clothes dryers, and bathroom exhaust fans can pull deadly flue exhaust backward down the chimney right into your basement (flue backdrafting). Understanding the visual, olfactory, and mechanical warning signs of a cracked heat exchanger or backdrafting water heater / furnace flue prevents mass household carbon monoxide poisoning and basement flame rollout fires.

Do this now

If your carbon monoxide alarm sounds, if you smell a sharp, eye-stinging metallic or formaldehyde odor coming from your heating vents, or if you see flames rolling out the front of your furnace cabinet, execute these six steps immediately:

  1. Evacuate all people and pets to fresh outdoor air immediately if CO alarms sound or symptoms appear: If a carbon monoxide alarm is beeping (typically 4 loud chirps, a pause, and 4 chirps), or if household members feel dull frontal headaches, dizziness, nausea, or sudden flu-like lethargy while the heat is running, get everyone outside immediately.
  2. Switch the furnace thermostat to OFF and shut off the emergency furnace power switch: If no one is symptomatic and the CO alarm is not sounding in an IDLH emergency, turn your wall thermostat mode to OFF and flip the red-plate "Emergency Furnace Shutoff" toggle switch (located on the side of the furnace or at the top of the basement stairs) to OFF.
  3. Close the quarter-turn natural gas or propane shutoff valve on the furnace supply pipe: Locate the rigid black iron gas pipe entering the side of the furnace cabinet and turn the manual brass valve handle 90 degrees (one-quarter turn) so the handle sits perpendicular (crosswise) to the pipe.
  4. Call emergency dispatch from outside if anyone has symptoms or if flames rolled out: Call your local emergency numbers (911 in the United States and Canada, 112 across the European Union, 999 in the United Kingdom) from outside the building. Firefighters carry parts-per-million electrochemical gas meters and thermal cameras to locate flue leaks and administer high-flow oxygen.
  5. Never reset a tripped manual Flame Rollout Switch yourself: If your furnace stops heating because a manual-reset Flame Rollout Safety Switch tripped above the burner box, do not press the tiny button on the switch to restart the furnace. A rollout switch only trips when 900-degree-Celsius flames are shooting backward out of the heat exchanger tubes due to a severe crack or blocked chimney flue.
  6. Do not run the furnace again until a licensed HVAC technician performs a combustion analysis: Never operate a "red-tagged" or suspect furnace "just overnight to stay warm." Use UL-listed electric space heaters plugged directly into wall outlets while awaiting heat exchanger replacement.

Why carbon monoxide has zero smell, yet incomplete combustion smells like pungent aldehydes

Pure carbon monoxide (\(CO\)) is 100 percent odorless, colorless, and tasteless; you can never smell carbon monoxide itself. However, when a natural gas or propane furnace burns poorly inside a cracked, rusted, or soot-plugged heat exchanger, the starved flame simultaneously produces aldehydes (such as formaldehyde and acetaldehyde). Aldehydes have an unmistakable, sharp, acrid, eye-watering, metallic or "burning radiator / sour exhaust" odor that blows directly out of your floor or ceiling heating registers. If you smell a sharp, stinging chemical or exhaust odor from your heating vents, treat it as an immediate warning that lethal odorless carbon monoxide is also pouring into your rooms.


Tactical decision tree for furnace heat exchanger cracks and flue backdrafting

Use this operational decision tree to evaluate furnace flame anomalies, vent odors, rollout trips, and chimney backdrafting.

flowchart TD
    Start["Furnace Anomaly: CO Alarm, Strange Vent Odor, Yellow Flames, or No Heat"] --> AlarmCheck{"1. Is a CO alarm sounding OR does anyone have headache, nausea, or dizziness?"}

    AlarmCheck -->|"Yes: Active CO exposure"| EvacOut["Evacuate All People & Pets Outside Immediately; Leave Doors Open on Way Out"]
    EvacOut --> Call911["Call 911 / 112 / 999 and Gas Utility Emergency Line from Outside"]

    AlarmCheck -->|"No: Physical or mechanical symptom on furnace"| SymptomType{"2. What warning sign did you observe on the furnace or vents?"}

    SymptomType -->|"Flames flickering/waving when main blower fan kicks on"| CrackSign["Classic Sign of a Cracked Heat Exchanger (Blower Air Pressurizing Burners)"]
    SymptomType -->|"Yellow/orange lazy burner flames + black soot streaks"| IncompleteComb["Incomplete Combustion: Plugged Secondary Heat Exchanger or Blocked Flue"]
    SymptomType -->|"Manual Flame Rollout Switch tripped OR scorched front door"| Rollout["CRITICAL FIRE & CO HAZARD: Flames Shooting Out Front of Burner Box"]
    SymptomType -->|"Hot exhaust spilling out draft hood or melted plastic rings on water heater"| Backdraft["Chimney Flue Backdrafting into Basement / Utility Room"]

    CrackSign --> ShutDown["Switch Thermostat OFF + Flip Red Furnace Power Switch OFF + Turn Gas Valve 90° OFF"]
    IncompleteComb --> ShutDown
    Rollout --> ShutDown
    Backdraft --> ShutOffExhaust["Turn Off Exhaust Fans/Dryer; Open Window 5 cm (2 in); Shut Off Appliance Gas Valve"]

    ShutDown --> CallHVAC["Do NOT Restart Furnace; Call Licensed HVAC Technician for Combustion & Camera Test"]
    ShutOffExhaust --> CallHVAC

Visual and physical warning signs of a cracked heat exchanger

How can you tell if the hidden steel clamshell or tubular heat exchanger inside your furnace has cracked before a carbon monoxide alarm goes off? Look and listen for these five physical indicators:

1. Burner flames suddenly dance, wave, or flutter when the main blower fan turns on

When your thermostat calls for heat, a furnace ignites its gas burners first and waits 30 to 60 seconds for the metal heat exchanger to warm up before switching on the large indoor circulating blower fan at the bottom of the cabinet.

  • Healthy intact heat exchanger: While the burners are running alone, the flames are steady, crisp blue cones roaring smoothly into the heat exchanger tubes. When the big indoor blower fan kicks on 45 seconds later, the burner flames do not move or change shape at all, because the blower air is completely sealed on the outside of the steel tubes.
  • Cracked or split heat exchanger: The exact second the large indoor circulating blower fan kicks on (with a loud whoosh of air), high-pressure household air from the blower forces its way through the crack into the inside of the combustion tube, or sucks combustion gases out. Looking through the small round glass inspection sight-port on the furnace door, you will see the blue burner flames suddenly waver, dance side-to-side, turn yellow-orange at the tips, or push backward toward the front of the furnace the instant the blower motor engages.

2. Lazy yellow or orange flames instead of crisp blue jets

A properly adjusted natural gas or propane atmospheric or induced-draft burner burns with a tight, crisp, roaring blue flame (sometimes with tiny pale-blue inner cones).

  • Exception: If you are running an ultrasonic cool-mist humidifier in the house using hard tap water, dissolved calcium and sodium minerals in the indoor air will turn gas stove and furnace flames a bright, crisp neon orange (a harmless sodium/calcium spectral emission).
  • Dangerous yellow flame: If the furnace burner flames look lazy, wavy, candle-like, and bright yellow, the flame is starved of primary oxygen or impinging against a rusted, soot-choked heat exchanger wall. A yellow natural gas flame generates up to 1,000 to 4,000 parts per million (ppm) of carbon monoxide alongside heavy black carbon soot.

3. Black carbon soot streaks ("eyebrows") above the burner ports or flue

Inspect the sheet metal directly above the burner manifold and around the draft hood or flue pipe collar:

  • Clean natural gas combustion leaves zero black soot.
  • If you see feathery black carbon soot streaks (called "soot eyebrows") above the burner tubes, rust flakes mixed with black powder on the floor of the burner compartment, or white/greenish crusty tracks leaking down from the secondary condensing heat exchanger box, shut the furnace off immediately. Soot buildup rapidly plugs the narrow passages of modern fin-and-tube secondary heat exchangers, causing lethal flame rollout within days.

4. Tripped manual-reset "Flame Rollout Switch"

Every modern gas furnace has one or two small, button-sized thermal disc switches mounted on the metal bracket directly above the gas burners, wired in series with the 24-volt gas valve circuit. These are manual-reset Flame Rollout Switches (typically rated to trip open at 120 to 175 degrees Celsius / 250 to 350 degrees Fahrenheit).

  • Why a rollout switch trips: Under normal operation, the negative suction of the draft inducer fan (or chimney updraft) pulls 100 percent of the 1,000-degree-Celsius flames forward into the heat exchanger tubes. If a heat exchanger tube is plugged with soot/rust, if the steel clamshell has split wide open and blower air is pushing back against the flame, or if the chimney flue is blocked by a bird's nest or collapsed clay tile liner, the flames have nowhere to go. They roll backward out the front of the burner box, scorching the wiring harness and tripping the rollout switch to shut off the gas valve.
  • Why resetting it can burn down your house: Homeowners who watch DIY videos often take off the furnace door, find the tiny pop-out button between the two wires on the rollout switch, push it back in until it clicks, and walk away. Because the underlying blockage or cracked heat exchanger is still there, the furnace will continue rolling flames out into the cabinet until the wiring catches fire or the house fills with carbon monoxide.

Diagnostic comparison: healthy furnace vs. cracked heat exchanger vs. flue backdraft

Diagnostic Feature Normal Healthy Gas Furnace Cracked Primary / Secondary Heat Exchanger Blocked Chimney or Flue Backdrafting
Burner Flame Color & Shape Crisp, steady blue cones pulled straight into the heat exchanger tubes Steady blue until main blower starts, then flames wave, flutter, lift off ports, or turn yellow-orange Flames look lazy and wavering from the very start; may roll out the front of the burner box before blower starts
Odor from Supply Air Vents (Bedrooms / Living Room) Warm, neutral air (slight dusty smell only on the very first run of autumn) Sharp, pungent, eye-stinging aldehyde / metallic exhaust smell blowing straight out of floor/wall vents Exhaust smell strongest in the basement or utility room around the furnace and water heater; spreads upstairs later
Moisture & Window Condensation Normal low winter indoor humidity (30% to 40% RH) Sudden heavy water condensation fogging up indoor windows (combustion water vapor leaking into supply ducts) Condensation and melted plastic rings around the top draft hood of the basement water heater
Flue Draft Hood / Vent Pipe Behavior Strong upward suction pulling exhaust up the chimney; plastic draft rings intact Inducer fan runs, but CO in supply ducts exceeds 5 to 50+ ppm or flue CO exceeds 100 to 400 ppm air-free Hot, humid exhaust gases spill outward into the basement from under the draft hood; smoke match blows into the room
Safety Switch Tripping None Flame Rollout Switch or High-Limit Switch trips repeatedly Spill Switch (on draft hood) or Pressure Switch (on induced-draft furnace) locks out the burner

Chimney flue backdrafting and the "Depressurized House" syndrome

Even if your furnace heat exchanger is 100 percent intact without a single crack, your family can still be poisoned by carbon monoxide if your chimney or vent pipe backdrafts (flows backward down the chimney into the house instead of rising up to the roof).

1. Which appliances are most vulnerable to backdrafting?

Heating and hot water appliances are divided into two venting categories:

  1. Atmospheric natural-draft appliances (Highest Backdraft Risk): Older 80-percent-efficient furnaces, standard gas boilers, and millions of common natural gas tank water heaters have no motorized exhaust fan. Instead, they rely entirely on the natural buoyancy of warm exhaust gas rising up a metal B-vent pipe or masonry chimney (natural stack effect), decoupled at the top of the tank by an open cone called a draft hood (draft diverter). Because natural buoyancy exerts a tiny upward pressure of only 2 to 5 Pascals (0.01 to 0.02 inches of water column), any negative pressure inside the house easily overwhelms the chimney and sucks outdoor air down the flue.
  2. High-efficiency (90%+ AFUE) condensing sealed-combustion furnaces (Lowest Backdraft Risk): Modern high-efficiency furnaces use two sealed white PVC plastic pipes (one drawing combustion air directly from outdoors, and one using a motorized blower to push cooled 45-degree-Celsius / 115-degree-Fahrenheit exhaust outdoors through the sidewall). However, they face a different winter emergency: snow drifts, ice dams, or hoarfrost plugging the exterior PVC intake/exhaust goosenecks outside your house foundation.

2. How exhaust fans and fireplaces cause lethal backdrafting

In a tightly weather-stripped modern or remodeled home, running exhaust appliances pumps hundreds of cubic feet of indoor air per minute (CFM) outdoors:

  • A clothes dryer exhausts 150 to 200 CFM.
  • Two bathroom exhaust fans exhaust 100 to 200 CFM.
  • A gourmet kitchen range hood exhausts 300 to 1,200 CFM.
  • A wood-burning fireplace or wood stove roaring in the living room pulls 200 to 500 CFM up its chimney.

If all windows and doors are tightly shut in winter and no makeup air vent exists, these appliances create a negative indoor air pressure (vacuum) of -5 to -25 Pascals inside the house. To replace that exhausted air, your house sucks outdoor air down the path of least resistance: straight down your furnace and water heater chimney flue. When the gas water heater or furnace fires up against that cold downdraft, 100 percent of its carbon monoxide exhaust spills out from under the draft hood into your basement or utility closet.

MECHANICS OF CHIMNEY BACKDRAFTING IN A DEPRESSURIZED HOUSE:
   [Roof Chimney Cap]
          ||   <-- Cold outdoor air sucked DOWN chimney (-15 Pascals vacuum)
          ||
          \/
   +--------------+
   | /==========\ | <-- Open Draft Hood on Gas Water Heater / Atmospheric Furnace
   |  (CO Spills) |     Hot combustion exhaust cannot rise against downdraft;
   |  +--------+  |     spills out into basement / utility room
   |  | Tank / |  |
   |  | Burner |  |=========================> [Clothes Dryer + Range Hood + Fireplace]
   +--------------+                            Pumping 600 CFM of air OUT of tight house

3. How to spot backdrafting on your gas water heater in 5 seconds

Walk to your gas water heater right now and look at the cold-water and hot-water pipes on the very top of the tank next to the sheet-metal cone (the draft hood):

  1. Melted plastic grommet rings: Almost all residential water heaters have colored plastic trim rings (blue around the cold inlet pipe, red around the hot outlet pipe) sitting on the top lid of the tank. If those plastic rings are melted, warped, curled up, or browned, or if the green/black insulation foam inside the pipe holes is charred, your water heater has been backdrafting 200-degree-Celsius (400-degree-Fahrenheit) exhaust gases directly into your home.
  2. Soot or powdery white corrosion on the top lid: A light coating of black soot or flaky white/grey acidic condensation scale across the top metal jacket around the draft hood confirms chronic exhaust spillage.
  3. What causes physical chimney blockages:
  4. Collapsed terracotta clay flue tiles: When a modern furnace is vented into an old unlined brick chimney (or an oversized masonry chimney after an old oil boiler is removed), acidic water vapor condenses inside the cold brick chimney in winter, freezing and thawing until the mortar and clay tiles crumble and pile up at the base of the chimney, blocking the furnace breech connection ("orphaned water heater" or crumbling liner effect).
  5. Animal nests, leaves, or snow/ice caps: Squirrels, raccoons, chimney swifts, and wasps build dense nests inside uncapped chimney flues during summer; when you turn the furnace on in October, the flue is 90 percent plugged.

High-efficiency (90%+) condensing furnaces: plugged secondary heat exchangers and frozen PVC vents

If your furnace vents through white PVC or black ABS/polypropylene plastic pipes out the side of your house instead of a metal chimney, it has two heat exchangers: a primary tubular steel heat exchanger, and a secondary condensing heat exchanger (which looks like a car radiator made of tightly spaced stainless-steel or polypropylene-coated aluminum fins) that extracts latent heat by condensing acidic water vapor out of the exhaust.

  1. Delamination and plugging of polypropylene-lined secondary heat exchangers: Several millions of condensing furnaces manufactured in the 1990s and 2000s experienced premature corrosion where an internal plastic coating peeled off and plugged the narrow exhaust channels, causing the burners to starve for oxygen and generate thousands of parts per million of carbon monoxide alongside a strong, foul aldehyde smell.
  2. Blocked condensate trap or frozen exterior PVC pipes: A condensing furnace produces 20 to 40 liters (5 to 10 gallons) of slightly acidic liquid water every day, which drains out through a clear vinyl tube. If the condensate trap clogs with slime, or if a winter blizzard buries the exterior PVC intake/exhaust pipes in a snowdrift (or grows a solid icicle over the pipe mouth), the furnace's pneumatic pressure switch will shut the burners down. During heavy snowstorms, regularly clear snow and ice at least 30 centimeters (12 inches) below your exterior plastic furnace vents while keeping your hands and face out of the exhaust plume.

Professional HVAC combustion testing and carbon monoxide alarm placement

A homeowner or home inspector can never confirm a heat exchanger is safe by visual inspection with a flashlight alone, because 80 percent of the heat exchanger surface is hidden behind sheet-metal baffles and blower housings.

1. What a licensed HVAC technician must measure

When you call a certified heating technician (such as NATE-certified in the US, TSSA-certified in Canada, or Gas Safe Registered in the UK) to inspect a suspect furnace, make sure they perform three objective tests:

  1. Digital Flue Gas Combustion Analysis: Inserting a calibrated electrochemical flue gas analyzer probe into the exhaust test port before and after the main blower fan turns on. In a healthy natural gas furnace, undiluted (air-free) carbon monoxide in the flue must be under 50 to 100 ppm (usually 10 to 35 ppm), and ambient CO in the supply air ducts must be strictly 0 ppm. If oxygen (\(O_2\)) in the flue jumps upward or \(CO\) spikes when the indoor blower turns on, the heat exchanger is breached.
  2. Borescope / Endoscope Camera Inspection: Threading a high-definition fiber-optic video camera through the high-limit switch hole or burner ports to visually inspect the stress-riserdimples, eyelet welds, and first bends of every heat exchanger cell.
  3. Worst-Case Depressurization Draft Test (CAZ Testing): Turning on all household exhaust fans, the clothes dryer, and the range hood with interior doors closed, then measuring chimney draft pressure in Pascals with a digital manometer to verify the water heater and furnace still establish positive upward draft within 60 seconds.

2. Installing a low-level digital carbon monoxide monitor

Standard UL 2034 / EN 50291 residential carbon monoxide alarms are intentionally engineered to prevent nuisance trips: they will not sound an alarm below 30 ppm for 30 days, and at 70 ppm they wait 60 to 240 minutes before beeping. To catch a slow heat exchanger leak early, and to protect pregnant women, infants, older adults, and heart patients, install at least one low-level digital display carbon monoxide monitor (which displays real-time digital readings starting at 5 to 10 ppm and sounds an alert at 15 to 25 ppm) on every sleeping level of your home, placed at breathing height 1.5 meters (5 feet) off the floor.

3. Why plugged return air filters cause heat exchangers to crack in the first place

The single most common mechanical cause of a cracked residential furnace heat exchanger is chronic airflow restriction from a dirty air filter or blocked return vents:

  1. Thermal stress cycling above 260 degrees Celsius (500 degrees Fahrenheit): Your furnace heat exchanger depends on a continuous, high-volume stream of cool indoor return air (typically 1,000 to 1,600 cubic feet per minute) flowing over the steel tubes to carry away the intense heat of the gas burners.
  2. Short-cycling on the High-Limit Switch: When a homeowner forgets to change the disposable furnace filter for 6 months, or installs an overly restrictive ultra-high-MERV pleated filter and closes bedroom supply registers, airflow drops by 40 percent. The steel heat exchanger overheats past 95 degrees Celsius (200 degrees Fahrenheit) air temperature, causing the automatic High-Limit Safety Switch to shut the gas burners off while the blower keeps running to cool the metal down. Three minutes later, the burners fire back up, overheat the metal again, and shut off again ("short-cycling on limit"). Thousands of these violent thermal expansion-contraction shocks fatiguing the steel welds eventually rip a crack straight through the heat exchanger wall. Always replace standard 25-millimeter (1-inch) furnace filters every 30 to 90 days during heating season and keep at least 80 percent of your house's floor and wall vents wide open.

Taking a hands-on first aid and CPR course from the Red Cross, St John Ambulance, or a local accredited provider ensures you can recognize acute carbon monoxide poisoning and provide life-saving support while awaiting paramedics.


Frequently asked questions

Can you smell a cracked heat exchanger or carbon monoxide coming from your heating vents?

Pure carbon monoxide gas is completely odorless and colorless, so you can never smell CO itself. However, when a furnace has a cracked or soot-plugged heat exchanger, incomplete combustion of natural gas or propane simultaneously produces aldehydes, which are chemicals that have a sharp, pungent, metallic, eye-stinging or sour exhaust smell blowing out of your heating vents. If you smell an acrid exhaust or chemical odor from your vents, shut the furnace off and evacuate immediately.

What does it mean if my furnace burner flames waver or turn yellow when the blower fan kicks on?

If your furnace burner flames burn steady and blue during the first 45 seconds after ignition, but suddenly wave, dance, flutter, or turn yellow at the exact instant the large indoor circulating blower fan switches on, that is the classic signature of a cracked heat exchanger. High-pressure household air from the blower is forcing its way through a split in the steel heat exchanger wall directly into the burner chamber.

Why did the little button on my furnace's Flame Rollout Switch pop out, and can I push it back in?

A manual-reset Flame Rollout Switch only trips when 1,000-degree-Celsius burner flames shoot backward out the front of the furnace instead of going up the heat exchanger, caused by a severely cracked heat exchanger, a soot-plugged secondary coil, or a blocked chimney flue. You must never push the reset button back in to restart the furnace yourself, as doing so can ignite a basement fire or fill your home with lethal carbon monoxide.

How can I tell if my gas water heater or furnace chimney is backdrafting into my basement?

Look at the cold and hot water pipes on the top of your gas water heater right next to the metal exhaust hood cone. If the blue and red plastic trim rings around those pipes are melted, warped, or scorched brown, hot combustion exhaust has been spilling backward out of the chimney hood into your home instead of rising up the flue.

Can running a kitchen range hood, clothes dryer, or fireplace cause carbon monoxide poisoning?

Yes. In a tightly sealed house with all windows closed, running a powerful kitchen range hood, a clothes dryer, bathroom fans, or a wood-burning fireplace pumps hundreds of cubic feet of air outdoors every minute, creating a negative vacuum inside the house. That vacuum easily overpowers the weak natural updraft of an atmospheric gas water heater or 80-percent furnace chimney, sucking deadly carbon monoxide exhaust backward down the chimney into your living space.

If an HVAC technician says my heat exchanger is cracked, can they weld it or seal it with furnace cement?

No, it is illegal and extremely dangerous to weld, braze, or apply high-temperature furnace cement to a cracked residential furnace heat exchanger. Because the thin aluminized steel expands and contracts continuously under extreme thermal stress, any patch or weld will immediately crack open again along the brittle heat-affected zone; you must either replace the entire heat exchanger assembly with a factory part or replace the furnace.


Sources checked

  • United States Consumer Product Safety Commission (CPSC, United States): Carbon Monoxide Poisoning from Residential Heating Systems, Cracked Heat Exchangers, and Flue Gas Spillage Investigations.
  • National Fire Protection Association (NFPA, United States) and American Gas Association (AGA): NFPA 54 / ANSI Z223.1 National Fuel Gas Code (Category I to IV Venting, Draft Hood Spillage, and Combustion Air Requirements).
  • Health and Safety Executive (HSE, United Kingdom) and Gas Safe Register (United Kingdom): Unsafe Situations Procedure (GIUSP) for Flueless and Open-Flued Gas Appliances, Spillage Testing, and Heat Exchanger Integrity.
  • Technical Standards and Safety Authority (TSSA, Canada) and CSA Group (Canada): CSA B149.1 Natural Gas and Propane Installation Code and Carbon Monoxide Safety Bulletins on Delaminating Secondary Heat Exchangers.
  • Building Performance Institute (BPI, United States): Combustion Appliance Zone (CAZ) Worst-Case Depressurization Testing and Flue Gas CO Action Thresholds.